KAL455E
Addressable MCP, red, surface mount w/ glass, IP67
- Easy numeric addressing
- Loop powered
- Local test facility
- Aesthetically pleasing
- Local status indication
Related products
At a glance
Product overview
The KAL455 series manual call points are developed for manual alarm activation on addressable fire systems running Kilsen protocol. The KAL455E is an addressable manual call point for manual fire activation for outdoor use. Up to 125 KAL455 series devices may be installed on every loop. Device addressing is done via easy to use DIP switches.
Configuration
The KAL455E provides an LED indication as well as manual test facilities. The LED may be configured to inciate communication with the fire panel as confirmation of proper operation. Various accessories for all applications are available.
Application
Manual call points are normally used as a user interface to an automatic fire detection system. It allows the user a direct interface into the system, to create an alarm at a very early stage (possibly even before the fire system has detected the fire), or as a confirmation of a fire alarm.
Installation
The KAL455E is normally fixed on a wall at a height of 1.2 to 1.5 m from the floor. They are used at emergency exit points and at strategic locations outside a building (verify installation practices according to local regulations).
Details
- Easy numeric addressing
- Loop powered
- Local test facility
- Aesthetically pleasing
- Local status indication
- Part of family of I/O modules consisting of: - Conventional Zone Monitors - Digital Input Modules - Extinguishing Control Modules - Isolator Modules - Standard Manual Call Points - Output Units - Fire Door Controllers - Supervised Output Units
- Wide range of accessories
- Weatherproof
Technical specifications
| General | ||
|---|---|---|
| Status indication |
Red LED
|
|
| Compatibility |
Kilsen KL7A systems
|
|
| Addressing method |
DIP Switches
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Loop powered
|
|
| Operating voltage |
22 to 35 VDC
|
|
| Current consumption |
<250 µA (quiescent)
<2.5 mA (alarm)
|
|
| Cable specification |
0.8 to 2.5 mm²
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Microswitch
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
98 x 93 x 28 mm (L x W x H)
|
|
| Net weight |
187 g
|
|
| Colour |
Red
|
|
| Mounting type |
Wall mount
|
|
| Cable entries |
3
|
|
| Functional marking |
House on Fire
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-25 to +70°C
|
|
| Storage temperature |
-25 to +70°C
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Outdoor
|
|
| IP rating |
IP67
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 2
WEEE
|
|
| Certification |
EN54-11
|
|
Downloads
All downloadsDatasheet
Certificates
Installation sheet
CPD / CPR
Other EU certificate
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.