Skip to main content

NC-DPM-W

Conventional multisensor fire detector (White)
  • Supports drift compensation to enable good environmental adaptability
  • Self-diagnostic
  • Local test activation with reed switch
  • Chamber contamination checking
  • All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation
View all

Related products

At a glance

General

The DC-9101E combines photoelectric (optical) detection, fixed temperature and rate-of-rise detection technology. The smoke and heat sensors are integrated to provide a solution to a wide range of applications, allowing detecting of more complex fire types. Amongst these include are fire types generating black smoke as well as small particles fires such as those from burning alcohol.

Application

The detector supports installation on the GST DB-01 conventional detector base for standard applications, or the GST DB-01D diode base when head-out functionality to BS5839 standard is required. Detection sensitivities are programmable using the GST P-9910B device programmer.

Details

  • Supports drift compensation to enable good environmental adaptability
  • Self-diagnostic
  • Local test activation with reed switch
  • Chamber contamination checking
  • All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation
  • Configurable polling LED support
  • Remote indicator output
  • 2 Programmable smoke sensitivity levels

Technical specifications

General
Status indication
Red LED
User interface
Via LED - polling, fault, contamination and alarm
Compatibility
GST100A Series conventional CIEs as well as GST I-9319 Zone Monitor
Reset voltage
<1 VDC
Reset time
<10 s
Alarm levels
2
Connectivity
Zone connection - 2-core (polarity sensitive), RI connection - 2-core (polarity sensitive)
Electrical
Operating voltage
9.5 to 28 VDC (24 VDC typical)
Current consumption
<60 μA (Quiescent)
≤55 mA (Alarm)
Cable specification
>1.0 mm²
No. of cable cores
2
Terminals
4
Detection
Detection principle
Optical & Heat
Sensitivity
Programmable
Zone length
Panel dependent
Heat Class A2R
Activation temperature 62°C
Output
Remote alarm output
1
Physical
Physical dimensions
54.5 mm (including base) x 100 mm Ø
Net weight
±110 g
Colour
Traffic white (RAL9016)
Mounting type
Ceiling mount
Material (body)
ABS
Environmental
Vandal proof
No
Operating temperature
-10 to +50°C
Relative humidity
0 to 95% noncondensing
Environment
Indoor
IP rating
IP2x
Regulatory
Compliancy
CE
WEEE
Certification
EN54-5
EN54-7
Voluntary marks
BOSEC
Standards
LPCB