Skip to main content

2010-2-PIB-8I8O

Addressable fire panel accessory, Peripherals Interface Board, 8 inputs, 8 outputs
  • 8 supervised inputs
  • 8 supervised outputs
  • Option to externally power
  • Pluggable connectors
View all

Related products

At a glance

Overview

The 2010-2-PIB-8I8O Peripherals Interface Board is an accessory of the small to medium size intelligent addressable life safety control systems. In total there are 4 variants of this board. The 2010-2-PIB-8I8O is a reduced variant of the 2010-2-PIB and is perfect if your only looking for having additional supervised inputs and outputs to interface other electronic equipment on site.

Functionality

The 2010-2-PIB-8I8O Peripherals Interface Board provides eight inputs and outputs for compatible control panels. The board can be powered from the control panel or from an external power supply, providing 24 VDC to each of the supervised outputs. Inputs and outputs are supervised for short circuit and open circuit faults.

Mounting & connections

The board can be plugged directly on the front of the main board inside the big size control panel variants on top of the new release 3 chassis. No additional wiring is required. You can use the pluggable connectors to make your connections to the field wiring. Connect an external power supply to the board directly to reduce the load of your system.

Details

  • 8 supervised inputs
  • 8 supervised outputs
  • Option to externally power
  • Pluggable connectors

Technical specifications

General
Compatibility
Release 3 hardware / firmware
Electrical
Power supply type
VDC
Operating voltage
24 VDC
Current consumption
40 mA max.(standby)
4050 mA max. (activated)
Output
Output type and rating
500 mA at 25°C (activated, per output)
Physical
Form factor
Large
Physical dimensions
105 x 192 mm (W x H)
Net weight
142 g
Shipping weight
240 g
Mounting type
In cabinet
Environmental
Operating temperature
+5 to +40°C
Storage temperature
-20 to +50°C
Relative humidity
10 to 95% noncondensing
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-2, EN54-13
Input activation
Open circuit >20.2 kOhm
Quiescent 15 kOhm
Activated 60.2 Ohm to 8 kOhm
Short circuit <60.2 Ohm
End-of-line termination
Input (typical) EOL 15 kOhm, 1/4 W resistor
Output (typical) EOL 15 kOhm, 1/4 W resistor
Output (EN 54-13) EOL Class B (EN 54-13) device

Downloads

All downloads

Datasheet

Installation sheet

Certificates

Other EU certificate

CPD / CPR

If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.