2 pairs, FTP LAN cable, Category 5e (Enhanced), reels of 500 m
  • 2 x 2 x AWG 24/1 FTP, category 5, enhanced
  • Recommended for:
    - Advisor Masters panels
    - Networked fire panels and repeaters
  • Certified by SGS for the compliance to the ISO/IEC 11801 (certification n°30.35.94.203/4)
View all

At a glance

Cabling for transport of different types of information: LAN, traditional and digital telephony (ISDN), video images, alarms and controls.

Certification

In addition to a very high standard of workmanship needed to meet the latest international standards, which establish the rules for the wiring of commercial buildings, the connections in a network must guarantee the utmost flexibility and universality. They must be able to support the widest range of current and future protocols.

As a result, the transmission media must be specifically designed to meet these requirements. In this area, they have also taken on a very important role in gaining certification for these cables, from both SGS and independent laboratories, that is recognised at national and international levels.

Category 5 "enhanced" cable, tested up to 200 MHz

The idea of this new cable category, which has transmission tested up to 200 MHz, is that these cables can be used for high bit-rate data networks with greater flexibility and availability than ordinary Category 5 cables.

In addition, they are characterised by a level of immunity which permits good transmission in even the most severe AMC environments and which complies with all types of application with radiation limits.

When the ACR (Attenuation to Crosstalk Ratio) is insufficient, problems may arise due to high frequency EMC performances and insufficient return losses.

WCAT used with Advisor Master

When WCAT cable is used with the Advisor Master systems, the rules with respect to maximum length of the databus and the databus topology should be respected. See installation manuals for more details.

Details

  • 2 x 2 x AWG 24/1 FTP, category 5, enhanced
  • Recommended for: - Advisor Masters panels - Networked fire panels and repeaters
  • Certified by SGS for the compliance to the ISO/IEC 11801 (certification n°30.35.94.203/4)

Technical specifications

Shielding
Shielded
Yes
Shield
1 tinned copper D.W.26/1 AWG + AL/PET tape
Insulation type
Solid
Core
Conductor size
0.52 mm²
Conductor material
Bare copper AWG 24/1
Wire colours
White-blue+blue, White-orange+orange
Jacket
Jacket colour
Grey - RAL 7032
Jacket material
F.R. PVC
Electrical Characteristics
Nominal velocity of propagation
74 %
Max. propagation delay
4.8 nsec/m
Max. propagation delay skew
0.10 nsec/m
Test voltage
700 VAC per 1 min
Max. rating voltage
125 V (not for power purposes)
Insulation resistance
2 Gohm/km
Max.conductor DC resistance
16.8 ohm/100 m @ +20°C
Nominal (mutual) capacitance
47 pF/m @ 1 kHz
Max. capacitance unbalanced
100 pF/100 m @ 1 kHz
Characteristic impedance
100 ±15 ohm
Structural return loss
25 db @ 20 MHz, 23 dB @ 100 MHz, 20 db @ 200 MHz
Physical
Cable length
500 m
No. of wires
4
Min. bend radius
42 mm
Max. pull strength
10 kg
Outer dimensions
5.20 mm
Weight
30 kg/km
Environmental
Halogen free
No
Operating temperature
-20 to +75°C
Heat release
507 MJ/km